: ESS용PCS

GT(Grid-Tie)-Indoor

500kW/1MW/2MW/2.5MW

NCM and LFP high-voltage lithium batteries Supported products available
- NCM lithium battery operating DC voltage: 740-1100V
 - LFP lithium battery operating DC voltage: 730-1500V



Power module-based operation - Improved operating efficiency and product lifespan System design based on a 20-year lifespan Using Hybrid SIC IGBTs to minimize switching losses Round-trip efficiency: approximately 96%


Ramp Rate: Max 10ms High-Performance Power Quality Assurance P+R Controller - Reduces THD and imbalance compared to DQ Controller Drop Control Without Communication Lines Power Factor Control

 
 

Grid Support - FRT (Fault Ride Through) Function Real-time remote monitoring and diagnostics Independent built-in power manager Support for stable communication lines - Dual Gigabit Ethernet ports

SAVEEN GT Single Line Diagram

LIB (Lithum Ion Battery)
BMS (Batter Management System)
EMS (Energy Management System)
PMS (Power Management System)

SAVEEN GT 500/1000/2000/2500 Specification

Model
Unit
SAVEEN GT 500
SAVEEN GT 1000
SAVEEN GT 2000
SAVEEN GT 2500
Input side(Energy Storage)
Max.allowable DC Voltage
V
NCM 1000
NCM 1100,LFP 1500
NCM 1100,LFP 1500
NCM 1100,LFP 1500
Rated DC Voltage
V
570
740
740
740
DC Operating range
V
570 ~ 830
740 ~ 1100
740 ~ 1100
740 ~ 1100
Rated DC Current
A
965
1487
2973
3717
Output side(Grid)
Rated AC Voltage
V
350
440
440
440
AC Operating Voltage Range
V
± 10%
± 10%
± 10%
± 10%
Rated AC Current
A
825
1313
2625
3281
Rated AC Power
kW
500
1000
2000
2500
Grid Frequency
Hz
50 / 60
50 / 60
60
50 / 60
Power Factor cos(@rated)
-
1
1
1
1
cos range
-
± 0~1
± 0~1
± 0~1
± 0~1
Current Distortion(@rated)
%
< 3
< 3
< 3
< 3
Connection phase
-
3 phase 3 wire
Efficiency
Max.Efficiency
%
97.6
98
98
98
Round Trip Efficiency(Estimated)
%
93.6
97
96
96
Size & Weight
Size(W/H/D)
mm
2200/1800/750
3500/2350/1000
4300/2350/950
4800/2350/1000
Weight
kg
1600
3000
4000
4500
Ambient Operating Conditions
IP Protection Class
-
IP20
IP54
NEMA3R
IP54
Ambient Temperature
°C
-10 ~ +40
-20 ~ +60
-20 ~ +50
-20 ~ +60
Humidity
%
0 ~ 95
0 ~ 95
0 ~ 95
0 ~ 95
Max.Height Above Sea-Leavel
m
2000
2000
2000
2000
Communication 
Default
-
(BMS : Modbus RTU or CAN) / (EMS : Modbus TCP)
Optional
-
(BMS : Modbus TCP) / (EMS : DNP3.0,IEC61850)
Standards
EMC
-
EN61000-6-2,EN61000-6-4,En61000-3-3,EN61000-3-12,Complies with EMC standardsFCC Class AEN61000-6-2,EN61000-6-4,En61000-3-3,EN61000-3-12,Complies with EMC standards
Safety
-
IEC62477-1 

Conforms to standards

IEC62477-1
conformity
UL1741 SAj, CSA C22.2 No.107.1-16(cTUVus)
IEC62477-1
conformity
Protection
Ground Fault Detection Device
-
Optional
Optional
Optional
Optional
AC
-
MCCB
ACB
ACB
ACB
DC
-
DS
DS+fuse
DS+fuse
DS+fuse


The specifications and appearance images of this product may change in the future.