: Power Quality System

SC(Super Capacitor) 

Instantaneous power failure compensation system



300kW/450kW/600kW

STABLEEN SC compensates for voltage fluctuations during power outages and voltage drops using the energy stored in the SuperCapacitor.




Switches from current source mode to voltage source mode in the event of momentary power outages or voltage drops, providing seamless power to the load within 4ms. Thyristor, an ultra-high-speed semiconductor switching element, ensures seamless power supply. UL TRIA capacitors increase efficiency (guaranteeing faster response and longer lifespan compared to batteries). Complies with Samsung Power Vaccine standard compensation (100% 1-second complete power outage compensation performance).


Lower power consumption compared to double conversion UPSs / Over 98% rated operating efficiency (energy savings) Separate pre-charge module installed for extended UL TRIA capacitor life Maintenance-free operation (no need for periodic UPS battery replacement) Enables energy efficiency Outstanding performance for nonlinear loads (voltage THD below 3%) CE certified and various safety certifications

STABLEEN SC Single Line Diagram

SSW(Static Switch)

STABLEEN SC 300/450/600 Specification

Model
STABLEEN SC 300KVA
STABLEEN SC 450KVA
STABLEEN SC 600KVA
AC input
Input voltage
3P(TN) 208V/220V/380V/400V/440V±10%
Input usage frequency
50/60Hz ±5%

AC output (rated output during commercial operation)
Output voltage
Voltage : 3P(TN) 208V/220V/380V/400V/440V, frequency: 50/60Hz
Output current

208V(833A)
220V(787A)
380V(456A)

400V(433A)
440V(394A)

208V(1249A)
220V(1181A)
380V(684A)

400V(650A)
440V(590A)

208V(1665A)
220V(1575A)
380V(912A)

400V(866A)
440V(787A)

Instantaneous overload capacity

Less than 5 times the rated output current, 1 cycle: Based on the thyristor characteristics.

Load power factor
According to commercial input
AC output (rated output when inverter is running)
Output voltage
Voltage: 3P(TN) 208V/220V/380V/400V/440V, frequency: 50/60Hz
Output commercial frequency
50/60Hz±5%
Output current
Same as commercial operating current
Instantaneous overload capacity
1.1 times the rated current
load power factor
According to commercial input
AC output (inverter output specifications)
Output frequency
50/60Hz±5%
Output voltage waveform
sine wave
Total Harmonic Distortion (THD)
Less than 3% (linear full load)
Compensation standard voltage setting
정격전압 기준 10.0 % - 90.0% (default: 85%)
Return voltage setting
보상기준전압 + 정격전압의 (1.0% - 5.0% 범위), (default: 3%)
transfer time
<4ms(60Hz) / <5ms(50Hz)
reward time
정격부하에서 1초, 3초 이내(사용자 요구 조건)
Repetitive Compensation
0.1s   정전시 충전동작 없이 3회 연속 보상 가능
Protection function (inverter protection)
Overcurrent protection

Switching after By-Pass switching with internal By-Pass Switch

Overvoltage protection

Switching after By-Pass switching with internal By-Pass Switch

Protection function (load protection)
Inverter low voltage output protection

Switching after By-Pass switching with internal By-Pass Switch

Inverter malfunction protection

Switching after By-Pass switching with internal By-Pass Switch

Alarm (HMI settings)
In case of overvoltage, overload, or system fault
Signal output
System Fault
1a1b Voltage-free contact
Sag Event
1a1b Voltage-free contact
Operating environment
Place of use
For indoor use
Ambient operating temperature
-10℃~40℃
Ambient humidity
0%~95% (no condensation)
Cooling method
Forced wind cooling
Withstand voltage

Compliant with IEC-62040-1

Appearance
STABLEEN SIZE WxDxH(mm)
3300 x 800 x 2000
3500 x 800 x 2000
2800 x 1610 x 20
STABLEEN WEIGHT(kg)
2400
2600
3500
MBP SIZE WxDxH(mm)
800 x 800 x 2000
800 x 800 x 2000
800 x 1610 x 2000
MBP WEIGHT(kg)
300
350
600
Monitoring
Product specifications
7"   TFT/LCD Touch Screen
STATUS

Status of voltage, current, frequency, output power, error/warning messages, events, SAG TRACE

Sag EVENT

When a Sag EVENT occurs, history (occurrence time, Sag intensity, Sag duration, etc.) is saved.


Communication
DATA communication
TCP/IP